Nitrogen Generator PLC Control System Debugging Guide
“Master the three steps for PSA nitrogen generator PLC debugging: preliminary hardware program double check, mid-term verification of signals/logic/closed loop/interaction in four stages, and final attention to safety backup. Follow this process, and even beginners can make this ‘industrial heart’ operate stably.”
As a key gas source equipment in the industrial field, the stability and reliability of the nitrogen generator directly affect the normal operation of the production line. The PLC control system, as the “brain” of the entire nitrogen generation system, is responsible for coordinating core processes such as adsorption tower switching, valve actions, and parameter monitoring. Newbies need to follow the principle of ‘prepare first, then step by step, and finally verify’ to avoid equipment failure due to operational errors. This article will present the debugging steps process of the mainstream PSA (Pressure Swing Adsorption) nitrogen generator PLC control system.

PSA Oxygen Generator
I. Pre-dial Preparation: Three Core Checks Must Be Completed
The preparation before debugging is the foundation for ensuring the safety and efficiency of the nitrogen generator. The following three checks must be completed:
Hardware connection check: Confirm that the PLC host and I/O module, pressure/flow/purity sensors, and electromagnetic valves, fans, air compressors, etc., have no loose or short circuits in the wiring; pay special attention to the positive and negative polarity connections of the electromagnetic valves to avoid reverse connection and burning of the coils.
Power and Ground Check: Turn on the power supply of the PLC control system and observe whether the power indicator light is normal; check the reliability of equipment grounding to prevent static electricity or interference from affecting signal transmission.
Program and Parameter Verification: Download the nitrogen generation machine control program to the PLC through the programming cable, and verify the matching of the program version and equipment model; confirm the initial values of core parameters such as adsorption time, pressure relief time, nitrogen purity setting value, and pressure upper and lower limits, ensuring they are consistent with the equipment manual.

II. Step-by-step Debugging: Four stages from single machine to linkage
Stage 1: Manual I/O Point Testing – Verify “Signal Path”
Through the “forced I/O” function of the PLC programming software, manually test whether the input signals and output actions are normal. This is the core basis of debugging:
Input point testing: Simulate sensor signals (such as short-circuiting the input point to simulate pressure compliance), observe whether the corresponding input point status changes from “OFF” to “ON” in the PLC software to ensure accurate sensor signal transmission.Output point testing: Force the PLC output point action (such as the “input point of the adsorption tower A inlet valve” being “ON”), observe the actuation of the corresponding solenoid valve and the lighting of the indicator light, and measure the voltage at the output terminal with a multimeter to ensure it is normal.
Stage 2: Single Cycle Action Debugging – Verify “Process Logic”
The core process of the PSA nitrogen generation machine is “adsorption – pressure relief – uniform – adsorption”, and it is necessary to test the smoothness and timing of each valve action in a single cycle:
Set the PLC to “single cycle operation” mode, and observe whether the actions of the inlet/exit/pressure equalization valves of adsorption tower A and B follow the set sequence (such as A adsorption when B is pressure relief, and then both towers equalize pressure).
Use a stopwatch to check the time of each stage (such as the adsorption time set to 120 seconds), and if the actual deviation from the set value exceeds ±2 seconds, adjust the program timer parameters.
Stage 3: Parameter Closed-loop Debugging – Verify “Automatic Control”
Connect the actual sensor signals and test whether the PLC can automatically adjust the equipment operation status based on parameter changes:
Pressure closed-loop: When the system pressure reaches the set upper limit (such as 0.8 MPa), the PLC should automatically close the air compressor inlet valve; when the pressure is lower than the lower limit (such as 0.6 MPa), it should automatically open the inlet valve, and observe whether the pressure changes are stable within the set range.
Purity closed-loop: If equipped with a nitrogen purity analyzer, when the purity is lower than the set value (such as 99.9%), the PLC should issue an alarm signal and adjust the adsorption time; when the purity is达标, the alarm is removed, and verify whether the automatic regulation logic is effective.
Stage 4: Linked Trial Run – Verify “Overall Synergy”
Link the nitrogen generation machine with the front-end air compressor, rear-end storage tank, etc., and conduct a continuous trial run for no less than 30 minutes:
Observe whether the equipment can automatically complete the start-up (air compressor → dryer → nitrogen generation machine), operation, and shutdown processes without stalling or incorrect actions.
Record the key parameters (nitrogen purity, pressure, flow rate) during the trial run, confirm that they are all stable within the qualified range, and check whether the temperatures of each module in the PLC control cabinet and the operation of the cooling fan are normal.
III. Debugging Precautions
1. During the debugging process, wear insulating gloves to avoid live operation; when dealing with electromagnetic valves and motor-type actuators, disconnect the load power supply first before checking the circuit.
2. After modifying the program each time, back up the original program to prevent errors in modification that cannot be restored.
3. After the debugging is completed, encrypt the PLC program and save a copy, and record the final determined parameter values to facilitate subsequent maintenance.
In conclusion, through the above steps, beginners can gradually complete the debugging of the PLC control system for the nitrogen generation machine. In actual operation, it is necessary to adjust flexibly according to the manual and on-site conditions to ensure that the nitrogen generation machine, this “industrial heart”, can continue to beat stably, reliably, and efficiently in the future, providing a continuous supply of high-quality gas for production.